OIL SEALED LIQUID RING PUMPS
DUPLEX BASE MOUNTED VACUUM SYSTEMS
Furnish and
install, where shown on the drawings a prefabricated duplex base mounted
oil sealed liquid ring vacuum system model____________ as manufactured
by EMSE Corporation, Fairfield, NJ (1-800-935-EMSE)
The unit furnished shall be a standard
catalog item of the supplier regularly engaged in the business of providing
packaged systems for hospitals and laboratories and shall meet and exceed the
requirements of NFPA 99.
The package shall include two oil sealed liquid ring vacuum pumps and associated equipment, one vertical ASME tank and one duplex control panel. All components shall be completely pre-piped and pre-wired to single-point service connections. All interconnecting piping and wiring shall be completed and operationally tested prior to shipment. Provide liquid tight conduit, fittings and junction boxes for all control and power wiring.
The medical pump system shall require neither seal water, purge water, nor chilled water. The pumps shall not have wearable vanes. They shall be totally air cooled, positive displacement, non-pulsating, capable of passing fluids and soft solids without damage.
Each vacuum pump shall be driven by a ____ HP, 3 phase, 60 cycle, ______ volt, 1750 RPM induction type motor. Each pump shall have a capacity of _______ SCFM at 19"HG.
The system shall include the following accessories for each pump: inlet check valve of bronze construction, inlet isolation valve, exhaust separator equipped with a two stage coalescing filter element, sight level and back pressure indicators, separator drain valve, air-to-sealant heat exchanger with sealant line thermometer and isolation valve, thermal malfunction switch and vacuum control switch. Provide flexible connectors on inlet and exhaust of each pump as well as copper tubing with shut-off cock for gauge and vacuum switches.
The sealing fluid shall have a minimum life of 10,000 hours of operation or two years (whichever comes first) and shall be capable of killing bacteria at normal operating temperatures.
The system shall include a 200 gallon vacuum storage tank of
ASME construction. The tank shall be rated for full vacuum service and shall be
equipped with a valved by-pass, vacuum gauge and a manual tank drain. The inside of the tank shall be coated for rust
protection with a two component coating which provides a hard, durable lining.
Provide vibration mounting per NFPA 99.
The system shall include a UL listed control panel in a NEMA 12 enclosure with the following accessories for each pump:
Externally operable
The vacuum system shall be guaranteed in writing by the manufacturer for a period of 18 months from the date of start-up or 24 months from the date of shipment (whichever comes first) against defects in design, materials, or construction. In addition, the bare pumps shall be guaranteed for 5 years from the date of shipment.
The service of a factory trained representative shall be made available at the jobsite to check installation, start-up and instruct operating personnel in the proper operation and maintenance.